Locked Re: LocoBuffer jumpers


 

The code _requires_ that echo be on. It listens to the incoming messages, including the echo'd ones it transmitted, to figure out the order in which things actually happened on the LocoNet. If you try to run it with echo off, various operations (including programming) will probably hang.

Bob

At 11:20 AM -0800 11/6/02, Peter Ely wrote:
And John recommends Echo be on.

..P

-----Original Message-----
From: Robin Becker [mailto:rbgroups@...]
Sent: November 6, 2002 9:38 AM
To: jmriusers@...
Subject: [jmriusers] LocoBuffer jumpers


Someone asked about the locobuffer jumper settings. Here's
the info based
on the schematic John Jabour posted:

JP1 Baud rate
1-2 19200
2-3 57600

JP2 Echo
1-2 off
2-3 on

JP3 Operating Mode
1-2 MS100 compatibiity mode
2-3 LocoBuffer mode

JP4, JP5 Programming
1-2 Normal
2-3 Program

Notes:
1. I think that you need to cycle power after moving the
jumpers before the
changes take effect.
2. JP4 and JP5 should always be 1-2 unless you are
reprogramming the PIC.


Robin Becker
Tucson, AZ

D&RGW Model Railroad Layout