Keyboard Shortcuts
ctrl + shift + ? :
Show all keyboard shortcuts
ctrl + g :
Navigate to a group
ctrl + shift + f :
Find
ctrl + / :
Quick actions
esc to dismiss
Likes
- Crestron
- Messages
Search
Re: Sonos control is still working?
Just curious if anyone is using the "offline" output on the Sonos Device module.? I haven't seen a case yet when a Sonos end point gets dropped and the "offline" output doesn't go high.? I would think you could OR all offline outputs on your Sonos Device modules and if the output of the OR goes high, reboot the system after a predetermined time.?
Like CO Cowboy, it hasn't been a big issue for me and like him, I am not doing any grouping.? Instead, If I see the Sonos is grouped via the Crestron module, I display a message that the room is grouped and to? use the Sonos app instead with a link to the Sonos App. Also, I make sure if there is an Ethernet connection to the Sono, I turn off WiFi in the Sonos Setting as I have seen countless cases were Sonos will switch to WiFi -- even if it has a much better Ethernet connection.? Possibly when it switches Ethernet adapters, it screws up the Crestron module. |
Re: Sonos control is still working?
About 50% of my systems are like that...
The other 50% are a problem... Haven't found anything unique about them...3 and 4-series, various FW versions, various vintages, various network hardware, etc., etc. The good sites have same/similar stuff, no discernable differences. |
Re: HZ2 for 5 or 6way Lighting Load Circuit
You can add as many KPEX devices as you want and just make them "programmatically" control the load.
Just connect them to hot power only and ignore the traveler. We do this quite often with the Cameo (Word Up) line of dimmers when we want more that a single load control. Good luck, Brian |
Re: Sonos control is still working?
This is all really odd, as I have several (probably 20) systems out there running Sonos, with no issues.
I've had a few fail, but after they are replaced with a Port they March on, without a programming change. I do recall, it took me a bit to master an initialize startup, but after that has been great. [Side note - I'm not using any groupings, or other features. Just favorites, being selected from the smart graphics. ] |
Re: Zoom with Flex Systems
Hoping this is not too off topic but have you utilized AirMedia with a Flex Zoom Room system? I have followed all the guides to put the AirMedia into "Flex Mode" but I cannot seem to get the Flex (UC-PR) to switch to the AirMedia content. All AirMedia apps etc show as connected but I never get the content switch at the display. Just continue to see the Zoom home page at the display (output of UC-ENGINE).
|
Is matt_rasmussen_2000 still around here? Roku module help needed
Using matt_rasmussen_2000's Roku 3 Series release module fromt he file section and it works great but getting a bunch of exceptions in the error log. A sample of the errors:
? 381. Error: SimplPlus[App01] # 2024-05-01 13:41:21 # em.Int32 aPort) [0x0007b] in <997da83ff2c248aabfb92e2f07fded5d>:0 ? at Crestron.SimplSharp.Net.Client.GetConnection (System.Net.IPAddress aHost, System.Int32 aPort) [0x00390] in <997da83ff2c248aabfb92e2f07fded5d>:0 ? at Crestron.SimplSharp.Net.Client.Co ? 382. Error: SimplPlus[App01] # 2024-05-01 13:41:21 # arp.Roku.Key (System.String ipAddress, System.String keyValue) [0x00032] in <e4b5925d8c344cfeb7ea59a65434d500>:0 ? at UserModule_ROKU_3_SERIES_ENGINE_20170609.UserModuleClass_ROKU_3_SERIES_ENGINE_20170609.KEYPRESS_OnPush_3 (System.Object __EventInfo__) [ ? 383. Error: SimplPlus[App01] # 2024-05-01 13:41:21 # ec740ddbe85b3e9927a2cfd>:0 ? at Crestron.SimplSharp.Net.Connection.DataSocketConnect (System.Net.EndPoint aEndPoint) [0x00081] in <997da83ff2c248aabfb92e2f07fded5d>:0 ? at Crestron.SimplSharp.Net.Connection.Connect (System.Net.IPAddress aIPAddress, Syst ? 384. Error: SimplPlus[App01] # 2024-05-01 13:41:21 # 0x00089] in <501afcc6360c4a41b4d89c3ce6aa3a59>:0? ? 385. Error: SimplPlus[App01] # 2024-05-01 13:41:21 # ec740ddbe85b3e9927a2cfd>:0 ? at Crestron.SimplSharp.Net.Connection.DataSocketConnect (System.Net.EndPoint aEndPoint) [0x00081] in <997da83ff2c248aabfb92e2f07fded5d>:0 ? at Crestron.SimplSharp.Net.Connection.Connect (System.Net.IPAddress aIPAddress, Syst ? 386. Error: SimplPlus[App01] # 2024-05-01 13:41:21 # nnect (System.Net.IPAddress aHost, System.Int32 aPort) [0x00070] in <997da83ff2c248aabfb92e2f07fded5d>:0 ? at Crestron.SimplSharp.Net.Client.Connect (System.String aHost, System.Int32 aPort) [0x00078] in <997da83ff2c248aabfb92e2f07fded5d>:0 ? at Crestro ? 387. Error: SimplPlus[App01] # 2024-05-01 13:41:21 # n.SimplSharp.Net.Http.HttpClient.GetHttpConnection (System.Boolean aSecure, System.String aHost, System.Int32 aPort) [0x00280] in <997da83ff2c248aabfb92e2f07fded5d>:0 ? at Crestron.SimplSharp.Net.Http.HttpClient.TryDispatch (Crestron.SimplSharp.Net.Http. ? 388. Error: SimplPlus[App01] # 2024-05-01 13:41:21 # em.Int32 aPort) [0x0007b] in <997da83ff2c248aabfb92e2f07fded5d>:0 ? at Crestron.SimplSharp.Net.Client.GetConnection (System.Net.IPAddress aHost, System.Int32 aPort) [0x00390] in <997da83ff2c248aabfb92e2f07fded5d>:0 ? at Crestron.SimplSharp.Net.Client.Co ? 389. Error: SimplPlus[App01] # 2024-05-01 13:41:21 # HttpClientRequest aRequest) [0x00477] in <997da83ff2c248aabfb92e2f07fded5d>:0 ? at Crestron.SimplSharp.Net.Http.HttpClient.Dispatch (Crestron.SimplSharp.Net.Http.HttpClientRequest aRequest) [0x00180] in <997da83ff2c248aabfb92e2f07fded5d>:0 ? at Roku_SSh ? 390. Error: SimplPlus[App01] # 2024-05-01 13:41:21 # em.Int32 aPort) [0x0007b] in <997da83ff2c248aabfb92e2f07fded5d>:0 ? at Crestron.SimplSharp.Net.Client.GetConnection (System.Net.IPAddress aHost, System.Int32 aPort) [0x00390] in <997da83ff2c248aabfb92e2f07fded5d>:0 ? at Crestron.SimplSharp.Net.Client.Co ? 391. Error: SimplPlus[App01] # 2024-05-01 13:41:21 # Module S-4.2.2.1.4.1.1:S-1 : Roku_3_Series_Engine_20170609 at line 90: Unhandled Exception: System.Net.Sockets.SocketException (0x80004005): Connection timed out ?at System.Net.Sockets.Socket.Connect (System.Net.EndPoint remoteEP) [0x000b6] in <cde117694 ? 392. Error: SimplPlus[App01] # 2024-05-01 13:41:21 # ec740ddbe85b3e9927a2cfd>:0 ? at Crestron.SimplSharp.Net.Connection.DataSocketConnect (System.Net.EndPoint aEndPoint) [0x00081] in <997da83ff2c248aabfb92e2f07fded5d>:0 ? at Crestron.SimplSharp.Net.Connection.Connect (System.Net.IPAddress aIPAddress, Syst ? 393. Error: SimplPlus[App01] # 2024-05-01 13:41:21 # arp.Roku.Key (System.String ipAddress, System.String keyValue) [0x00032] in <e4b5925d8c344cfeb7ea59a65434d500>:0 ? at UserModule_ROKU_3_SERIES_ENGINE_20170609.UserModuleClass_ROKU_3_SERIES_ENGINE_20170609.KEYPRESS_OnPush_3 (System.Object __EventInfo__) [? |
HZ2 for 5 or 6way Lighting Load Circuit
Hi All!
I have the above hard wired wall switches, in a working lighting situation. ?I read the the Hz2 Dimmers and the Aux or KPEX are Gggod with up to a 4 way circuit. ?Any advice on a workaround or if anyone has added a greater number of the accessory device above? Thank you very much FURY -- Thank you very much FURY |
Re: Program load to processor - best practice
Yea agreed. ?we dont really work with 2 series anymore. ?they are so old that you wind up spending too much time troubleshooting. ?
It's more cost effective to just replace it with a modern processor than spend the man hours making the 2 series compile and load properly. ? I dont know actual numbers but I'm pretty sure a cheap RMC4 can run circles around a Pro2. ?Then the client has the added benefit of something thats under support and warranty again. |
Re: Program load to processor - best practice
I think in most cases, the it makes no difference if you erase first or just over write the program.? My understanding of the file system with flash is when ever you erase or replace a file, the original program gets mark as delete and it not recovered until the file system is compacted.? If the processor does not have enough unused flash to load the program, it will compact the file system to recover the lost storage.
However, I've seen some cases where some large programs are so busy that the cause the processor to crash when attempting to load a program.? In those cases, it is best to stop the original program first using the console command "STOPPROG" before loading the new program. The series 2 processors are getting quite old now and I have found issues when trying to compile/load programs/firmware for them with newer Crestron software -- in particular toolbox.? Some functions can only be done with Viewport -- the predecessor to Toolbox. So when I program a series 2, most of the time I use older versions of Crestron software and run them in a Virtual Box Window XP machine as some of Crestron's older software will not run with newer versions of Windows. |
Program load to processor - best practice
Still learning and have a question on loading new and/or updated programs to the control processor, in this case a 2-series on the AMS-AIP.?
What is the best practice when loading/updating the program, should the currently running program be stopped and then erased before the updated program is uploaded to the processor? I ask because sometimes when uploading the program toolbox says compacting file system which leads me to believe that it is adding the new program to NVRAM as opposed to replacing the currently running program. Just want to do thing right so hopefully one of you will have the answer. Thanks, Don |
Re: Sonos control is still working?
I rarely integrate for clients because of past experience. I do have Sonos integrated at home and used to have issues with communications failing but for the last couple of years the only time I might have to reboot is after a Sonos update, I rarely have to reboot then.
|
Re: Weather processor V1.6
After reading the article, I'm not surprised I can't get it working.? If I'm reading this correctly, the new module is strictly smart graphics compatible.? the original system has 2 TPS4500's, 2 TPS6000's and a TPS6000L. With the old PRO2 and previous module and touch screen interface, all worked perfectly.? I am planning to upgrade all my tp's to Apple tablets.? I guess sooner then later now.
|
Re: Autonomics Modules
From their website
toggle quoted message
Show quoted text
Michael Restrepo | Owner Restrepo Innovations 825 Windham Court North Wyckoff, NJ 07481 Office | 201.925.0059 Direct | 201.952.4624 Email | mike@... Elite Pro Crestron Dealer Website | www.restrepoinnovations.com Instagram | www.instagram.com/restrepo_innovations Facebook | www.facebook.com/restrepoinnovations Twitter | www.twitter.com/innovationsmr CONFIDENTIALITY NOTICE: The contents of this email message and any attachments are intended solely for the addressee(s) and may contain confidential and/or privileged information and may be legally protected from disclosure. If you are not the intended recipient of this message or their agent, or if this message has been addressed to you in error, please immediately alert the sender by reply email and then delete this message and any attachments. If you are not the intended recipient, you are hereby notified that any use, dissemination, copying, or storage of this message or its attachments is strictly prohibited. On Apr 29, 2024, at 3:18?PM, Eric Luckart via groups.io <eluckart@...> wrote: |
to navigate to use esc to dismiss