Re: DMPS Video Lag

 

try deactivate any video processing.? like 120hz activation.? HDMI av or HDMI PC.

don't remember which brand I have to disable some options.

{Paf} Mobile

Le 1 oct. 2014 18:40, "ephrain81@... [Crestron]" <Crestron@...> a ¨¦crit :

?

It is the TV causing that. Some consumer TV's lag on the video processing. I could not figure out a way to correct. Just use a different model next time.


Re: SunBriteTV

Owain Price
 

The protocol which you can download from their website is very straightforward.



I've never bothered creating a module because I have only used them as a basic endpoint. If you need help along the way let me know.


Thanks,
Owain Price
The Sound Room
St. Louis, MO

From: Crestron@... [mailto:Crestron@...]
Sent: Wednesday, October 01, 2014 11:48 AM
To: Crestron@...
Subject: [Crestron] Re: SunBriteTV



did you ever get the module?
I'm looking for it now and can't find it either.


Re: DMPS Video Lag

 

It is the TV causing that. Some consumer TV's lag on the video processing. I could not figure out a way to correct. Just use a different model next time.


Re: DMPS Video Lag

Andrew Welker
 

Try putting the display into gaming mode or something similar. Most modern displays have a refresh rate that is much higher than the frame rate of the incoming video. This causes some of the processing that TB mentioned. It might not get rid of all the lag, but it might improve it greatly.

On Oct 1, 2014 5:23 PM, "lankford.patrick@... [Crestron]" <Crestron@...> wrote:

?

I have a DMPS-200 installed with a local PC going into one of the HDMI inputs and out of the DM output to a DM-RMC-SCALER to a 70 inch display. The customer is using the 70 inch display as their local monitor and is saying there is lag in the mouse when working. I have noticed the lag (mili-seconds) and TB claims this is normal video processing and no settings will correct the lag. Maximum cable run is probably 75' of DM cable.


Has anyone seen this before or know of a setting that might correct the lag??


Just trying to explore options.


Thanks


DMPS Video Lag

 

I have a DMPS-200 installed with a local PC going into one of the HDMI inputs and out of the DM output to a DM-RMC-SCALER to a 70 inch display. The customer is using the 70 inch display as their local monitor and is saying there is lag in the mouse when working. I have noticed the lag (mili-seconds) and TB claims this is normal video processing and no settings will correct the lag. Maximum cable run is probably 75' of DM cable.


Has anyone seen this before or know of a setting that might correct the lag??


Just trying to explore options.


Thanks


Re: Divisible Room GUI

 

I use two overlapping circles like a venn diagram for a combing icon.? Like this one:


On Wed, Oct 1, 2014 at 10:35 AM, bdige@... [Crestron] <Crestron@...> wrote:
?

Hi,

Does anyone have a standard divisible room icon that they do not mind sharing?

Thanks,

B



Re: New DSP

 

¿ªÔÆÌåÓý

Ditto on the Nexia/Audia.?

Tesira is the same concept except you get to create your own subscription name for feedback :).?


On Oct 1, 2014, at 1:00 PM, Andrew Welker andrew.welker@... [Crestron] <Crestron@...> wrote:

?

Just use Instance ID Tags instead of the DSP assigned tags. Then as long as the control gets the correct instance ID tag, then it'll work no matter what the instance ID is. I don't remember the last time I used the assigned instance id.

On Wed, Oct 1, 2014 at 2:53 PM, cyberbri24@... [Crestron] <Crestron@...> wrote:
?

I Like Biamp for its customization, Have yet to use the Forte but like the idea of the USB for the capability for adding Skype/Lync.... Hate how the instance ID can be lost if a tech deletes a control, then adds it back.


I Like Polycom SS, never had any issues.

I Love Clearone, from a control standpoint. Its nice to get realtime feedback and if you use Macros for control, it can be a rock solid solution. Just deployed about 50 of these in the summer with no issues or calls. Techs can go in after and tweak input/output/mixer levels and adjust a macro for even more control and it never effects the integrated controls. I actually have a standard DSP that can be loaded into a 840T and 880T. Started using Processing buss A, B, C, & D, Faders 1, 2, 3, & 4. This way if the job has a need for more than 8 sets of controls or levels to be tracked, I have the engineer make sure the system adds the 880T which allows for more processing. ?





--
In Him,
Andrew Welker



Re: D3 : Conditional logic for HRV bathroom fan controlled from multiple rooms

 

¿ªÔÆÌåÓý

Exactly. Variables are your friend.?


On Oct 1, 2014, at 1:02 PM, easton.altree@... [Crestron] <Crestron@...> wrote:

?

One more question. ?In each room, how would I add logic so that the FAN button on the KP will still send requests? ?I'm guessing that the Variable Editor might be of use here?


Re: Divisible Room GUI

 

¿ªÔÆÌåÓý

Lol. So true...


On Oct 1, 2014, at 1:23 PM, Jeremy Weatherford jweather@... [Crestron] <Crestron@...> wrote:

?

Some people, when confronted with a problem, think "I know, I'll use crosspoints."? Now they have two problems.




Just kidding... sort of.? Stolen from jwz.

On Wed, Oct 1, 2014 at 2:39 PM, cyberbri24@... [Crestron] <Crestron@...> wrote:
?

Same on different.


Use X-Points.




--
Jeremy Weatherford


Re: Divisible Room GUI

 

Some people, when confronted with a problem, think "I know, I'll use crosspoints."? Now they have two problems.




Just kidding... sort of.? Stolen from jwz.

On Wed, Oct 1, 2014 at 2:39 PM, cyberbri24@... [Crestron] <Crestron@...> wrote:
?

Same on different.


Use X-Points.




--
Jeremy Weatherford


Re: A Bunch of Used Crestron Gear

 

lol.? I'm not looking for top dollar.? I just want to reclaim the space.


Re: A Bunch of Used Crestron Gear

 

I think 600 would be fair.

jason


Re: D3 : Conditional logic for HRV bathroom fan controlled from multiple rooms

 

One more question. ?In each room, how would I add logic so that the FAN button on the KP will still send requests? ?I'm guessing that the Variable Editor might be of use here?


Re: New DSP

Andrew Welker
 

Just use Instance ID Tags instead of the DSP assigned tags. Then as long as the control gets the correct instance ID tag, then it'll work no matter what the instance ID is. I don't remember the last time I used the assigned instance id.

On Wed, Oct 1, 2014 at 2:53 PM, cyberbri24@... [Crestron] <Crestron@...> wrote:
?

I Like Biamp for its customization, Have yet to use the Forte but like the idea of the USB for the capability for adding Skype/Lync.... Hate how the instance ID can be lost if a tech deletes a control, then adds it back.


I Like Polycom SS, never had any issues.

I Love Clearone, from a control standpoint. Its nice to get realtime feedback and if you use Macros for control, it can be a rock solid solution. Just deployed about 50 of these in the summer with no issues or calls. Techs can go in after and tweak input/output/mixer levels and adjust a macro for even more control and it never effects the integrated controls. I actually have a standard DSP that can be loaded into a 840T and 880T. Started using Processing buss A, B, C, & D, Faders 1, 2, 3, & 4. This way if the job has a need for more than 8 sets of controls or levels to be tracked, I have the engineer make sure the system adds the 880T which allows for more processing. ?





--
In Him,
Andrew Welker



Re: AV2 and Rack2

 

Use the AV2 as the master, then drop a RACK2 in your crestnet devices as a Crestnet slave since you have no E-NET card. In the Rack2 info view in toolbox, you'll see where it has a Crestnet ID of "2". You need to change that to some other Crestnet ID (3 or higher) and it will show up on your AV2 crestnet network.

Goodluck,

Cyberbri


Re: New DSP

 

I Like Biamp for its customization, Have yet to use the Forte but like the idea of the USB for the capability for adding Skype/Lync.... Hate how the instance ID can be lost if a tech deletes a control, then adds it back.

I Like Polycom SS, never had any issues.

I Love Clearone, from a control standpoint. Its nice to get realtime feedback and if you use Macros for control, it can be a rock solid solution. Just deployed about 50 of these in the summer with no issues or calls. Techs can go in after and tweak input/output/mixer levels and adjust a macro for even more control and it never effects the integrated controls. I actually have a standard DSP that can be loaded into a 840T and 880T. Started using Processing buss A, B, C, & D, Faders 1, 2, 3, & 4. This way if the job has a need for more than 8 sets of controls or levels to be tracked, I have the engineer make sure the system adds the 880T which allows for more processing. ?



Re: Divisible Room GUI

 

Same on different.

Use X-Points.


Re: Divisible Room GUI

 

It's "just like that other divisible room".

On Wed, Oct 1, 2014 at 2:22 PM, Lincoln King-Cliby lincoln@... [Crestron] <Crestron@...> wrote:
?

There is a standard¡­every one is a little different.

?

--

Lincoln King-Cliby, CTS, DMC-E-4K/T/D

Commercial Market Director

Sr. Systems Architect | Crestron Certified Master Programmer (Gold)

ControlWorks Consulting, LLC

V: 440.449.1100 x1107 F: 440-449-1106 I:

Crestron Services Provider | Biamp Audia Certified | Extron Control Professional

?

From: Crestron@... [mailto:Crestron@...]
Sent: Wednesday, October 01, 2014 12:10 PM
To: crestron
Subject: Re: [Crestron] Divisible Room GUI

?




Sorry no, but I'm still laughing at the words "standard divisible room" being used consecutively....

?

On Wed, Oct 1, 2014 at 9:35 AM, bdige@... [Crestron] <Crestron@...> wrote:

?

Hi,

Does anyone have a standard divisible room icon that they do not mind sharing?

Thanks,

B

?






Re: Divisible Room GUI

 

¿ªÔÆÌåÓý

There is a standard¡­every one is a little different.

?

--

Lincoln King-Cliby, CTS, DMC-E-4K/T/D

Commercial Market Director

Sr. Systems Architect | Crestron Certified Master Programmer (Gold)

ControlWorks Consulting, LLC

V: 440.449.1100 x1107 F: 440-449-1106 I:

Crestron Services Provider | Biamp Audia Certified | Extron Control Professional

?

From: Crestron@... [mailto:Crestron@...]
Sent: Wednesday, October 01, 2014 12:10 PM
To: crestron
Subject: Re: [Crestron] Divisible Room GUI

?




Sorry no, but I'm still laughing at the words "standard divisible room" being used consecutively....

?

On Wed, Oct 1, 2014 at 9:35 AM, bdige@... [Crestron] <Crestron@...> wrote:

?

Hi,

Does anyone have a standard divisible room icon that they do not mind sharing?

Thanks,

B

?





Sony evi-d camera processor

 

So I was working with a VDO360 camera last week. There is a published crestron module on their website that I tried to use-It did not work well and zoom in and out did not work at all. So tried a different sony module (it uses sony visca protocol) the zoom also did not work on that module.I modified the module allowing for simple zoom in and out cause I had a lot of stuff to do as the install was out of the country and time was limited. When I got back I dug in a little bit and found that for zoom in and out the strings being sent to the cam for zoom were wrong

good example \x81\x01\x04\x07\x02\xFF this would indeed zoom in

bad string from modules??\x81\x01\x04\x07$\xFF?

? so for that last hex the module spits out ascii

it looks to me like the problem lies in the simpl+ module "sony EVI-D camera processor" ?all the modules including the published vdo360 have this simpl+ in common


has anyone encountered this before? maybe some simpl+ gurus can see why this happens.

I believe it occurs in the zoom speed section of the processor but it is not obvious to me where the error lies