Re: TCP Client Stopped working
I've seen this as well. I have a case open with TB right now for it. What I was able to narrow it down to was if you lose link on the CS side of the processor that is what breaks the TCP/IP client. I
By
brianmagrogan
·
#245686
·
|
Re: TCP Client Stopped working
I've seen this since the very first CP4N we installed right after they came out, and your experience sounds a lot like mine. In S+, you can leave it to stay connected and automatically reconnect and
By
jonathand@...
·
#245685
·
|
Re: TCP Client Stopped working
?FTR, I almost never turn the connect off with any device and have not had any particular issues until now...¡° Same here. Especially in my home/test-system, i?ve got a lot of TCP Clients in the
By
Thorsten K?hler
·
#245684
·
|
Crestron Home + DMP alarm lightweight integration?
#crestronapp
#crestron
Hi, I have a Crestron Home system and a DMP (XR 150/500) alarm. I understand that a full integration of the DMP system into Crestron seems not possible but is there a way to just have the alarm status
By
[email protected]
·
#245683
·
|
Re: TCP Client Stopped working
Olivier, Yeah, I'm not sure why I have a '1' on it (probably some legacy thinking...) at minimum, I usually make it an actual signal, that is driven by a '1', thru a buffer, so that I can at least
By
ckangis
·
#245682
·
|
Re: TCP Client Stopped working
I never use "1" on a TCPIP client module, I always use a connection manager to connect to the device when needed and close the connection after. This can be as short as a few milliseconds to send a
By
Olivier Royer
·
#245681
·
|
Re: Master 2022, no virtual option? WTF
OLH: 1001189, or just search online help for Masters. September 20-22, registration opens June 15th
By
Neil
·
#245680
·
|
Re: DM NVX creates a broadcast storm for ~2 minutes every ~ 30 minutes
A big shout out to Crestron_Programmer_84 for all his help!? The problem was resolved by turning off Spanning Tree Protocol the VLAN that is used for the NVX and other things being controlled.?
By
bryan_d_garcia
·
#245679
·
|
Re: Master 2022, no virtual option? WTF
has the date been released yet?
By
Shawn Fennell
·
#245678
·
|
Re: TCP Client Stopped working
Yeah, It definitely seems very intermittent, as I at least have not seen it before... In this case, I don't believe that the Vantage system was off-line at all (certainly not for hours/days) so it
By
ckangis
·
#245677
·
|
Re: TCP Client Stopped working
I¡¯ve seen an issue on my home system (PRO4) a couple times but not with enough frequency to get enough info for a proper bug report where if the Ethernet link is lost under some circumstances the
By
Lincoln King-Cliby
·
#245676
·
|
TCP Client Stopped working
Hi All, Wondering if others have seen this odd, intermittent behavior...and also a heads-up for others to watch out for it CP4 (v2.7000.00040) has a TCP client communicating with a Vantage System
By
ckangis
·
#245675
·
|
Re: DM-PSU-3X8-RPS is Discontinued
It¡¯s not as elegant (or rack mountable) but I think some multiple of PW-5430DUS is your answer https://www.crestron.com/Products/Accessory/Power-Supplies/Power-Packs/PW-5430DUS -- Lincoln
By
Lincoln King-Cliby
·
#245674
·
|
DM-PSU-3X8-RPS is Discontinued
Anyone have any suggestions for a replacement device that will supply PoDM+ power to all ports on a 64x64 blade? Are we out of luck and stuck powering everything with wall warts? -JRW
By
jrw_96
·
#245673
·
|
bosch dcn ccub-ul
Hi All, Does anyone know where I can find configuration software for this unit? (bosch dcn ccub-ul) Thank you
By
Crestron_Programmer
·
#245672
·
|
Re: QSYS with Mat Klucznyk Github
Scott, I am currently using these module without any issues. Can you post a snippet of the Fader (one with issues) and Core module?
By
Brad Wykoff
·
#245671
·
|
Re: Calling a C# method from Simpl+
Thanks for the response and I was able to get this to work. Next: I am reading an XML document, converting to JSON (this works) and placing in a <List> but not certain how to get the list back to
By
Brad Wykoff
·
#245670
·
|
Re: Control for NP-PA803UL / new protocol?
I don¡¯t think 015. Power On is the actual command just the command number and name (if you look at other fields in the document there are hex bytes provided for e.g. DATA 02 and DATA 03. I think
By
Lincoln King-Cliby
·
#245669
·
|
Re: NVX vs. SVSI
Hi again Jeff, Sorry for the delayed response, it¡¯s been a busy week. Here are the answers to your follow-up questions: ? Does the current VLAN switching software allow for control of multiple
By
eoqualls
·
#245668
·
|
Re: Crestron Processor with 3rd Party Touch Panel?
If you can made custom HTML5 user interfaces on it, our WebSockets suite would be perfect for this application:?https://controlconcepts.net/product/cci_websocket_server_lite/
By
@MikeSpadafora
·
#245666
·
|