Re: Lutron QS Request Command <--Please someone help!!


 

It may work without the action specified, and default to action 1 on a query, but the protocol definitely shows the action being used with the query in their example.

--- In Crestron@..., "Siong P Low" <sp@...> wrote:

I am not 100% certain on this, but am pretty sure that the query command is "?OUTPUT,1&#92;n".

The Action number is only for actual commands:
For example, Action 1 is set output level
#OUTPUT,1,1,80,4,1&#92;n - this will set unit ID 01 to 80%, 4 sec fade, 1 sec delay
#OUTPUT,1,2&#92;n - will just raise the level of unit ID 01
... and so on.

The query command does not use the Action number, I believe.


--- In Crestron@..., "sevenstarokawari" <tabata@> wrote:

I am glad to get kind reply from you.
OK,,, i will try with "?OUTPUT,ALL_DEVICES,1"

Do you know what's the meaning of the last "1"
According to the manual, it says "Action Number"
I can't understand...


--- In Crestron@..., Eric Williams <ewilliams0305@> wrote:

Its been a while but instead of "1" try the commands using "ALL_DEVICES" as your integration Id. It will definitely work for polling not sure about setting levels.

-----Original Message-----
From: "sevenstarokawari" <tabata@>
Sent: ?€&#65533;3/?€&#65533;21/?€&#65533;2013 9:09 PM
To: "Crestron@..." <Crestron@...>
Subject: [Crestron] Re: Lutron QS Request Command <--Please someone help!!




--- In Crestron@..., "sevenstarokawari" <tabata@> wrote:

Would someone advise me the command to get all zone's brightness of Lutron QS simultaneously?
Actually I sent"?OUTPUT,1,1<CR><LF>", but nothing happens.
The Lutron QS ID of mine is "1"


Regards,