"But, I would think that if the motor is stalled it would draw "locked rotor amps" and this ought to trip a properly selected overload or fuse pretty much immediately.? Not so?"
Not so. A motor draws locked rotor current at start and long enough?to accelerate to near synchronous speed. There is a bit more to it than that but it's close enough. There must be a time delay in the overload to allow the motor to start at the locked rotor current; if there wasn't, you could never get the motor started without tripping the overload. Overloads are what we call an inverse time device. That means that the higher the current the faster it trip and the lower the current the slower it trips. Overloads do not trip instantaneously, they always take some time. In the USA, overloads are typically designed for 10, 20 or 30 seconds around 600% of motor current which is a typical locked?rotor current - at least the 3-phase units I am familiar with. Again, it's not quite that simple but close enough. Small single phase motors generally have a lower locked rotor current. The time to trip an overload is going to be longer. In many cases it is longer than the thermal capability of the winding insulation and will cause failure before the overload can react.? On Mon, Feb 1, 2021 at 12:10 PM Alan Muller < alan@...> wrote:
This is interesting information.?? I am NOT an
electrical engineer and claim no expertise in motor protection.?
Certain things jump out:
Many cheap Asian motors don't have enough information on the data plate
to select protection.? Or the claimed horsepower doesn't match the
current rating, or.....
The internal "klixon" type protectors are somewhat responsive
to both motor temperature and current draw.? A simple external?
"starter"--be it melting alloy or bimetal-- doesn't know how
hot the motor is, but only how much current it is drawing.? So
current draw could be within ratings but if the fan is loose or the air
passages clogged with debris, the motor could be cooking.
But, I would think that if the motor is stalled it would draw
"locked rotor amps" and this ought to trip a properly selected
overload or fuse pretty much immediately.? Not so?
My 4x6 gets only light use and I don't let it run unattended.? If I
were to use it more heavily I think I would install an IEC type bimetal
starter and back off the current adjustment until it tripped in normal
use, then turn it up a little.....? Is this sound thinking?
I also have a 14" wood cutting band saw.? The base (factory)
has no provision for ventilation of the motor.? This clearly would
not do for heavy use.
am
At 11:38 AM 2/1/2021 -0800, you wrote:
My stock Horror Freight 4x6 is
TEFC. I just went out and confirmed. The motor is finned and there is a
fan shroud over the rear. When running, the fan blows air over the fins
for cooling. It does not have any overload protection.
Now for my diatribe.
The best solution to prevent damaging a motor due to stalling isto be
present when operating. Leaving the machine unattended is why the motor
will burn up when stalled. I've said this before, overloads do not
adequately protect motors from a stalled position. They definitely don't
hurt but you cannot rely upon them to protect an unattended machine.?
I'm a retired registered electrical engineer with over 45 years of
experience who taught electrical system protection and have been an
expert witness in protection matters. There will always be anecdotal
evidence that suggests an overload will protect against a stalled
condition but I can present you with lots of technical data to show that
is not the case. The simplest explanation is that overloads are designed
for when the motor is running which means they are designed to trip while
the motor is still getting fan cooling. A stalled condition has no
cooling and must trip much faster because of it. There is thermal lag
between the motor winding and any thermal sensing device which may be in
the motor. This lag can be long enough to either damage or fail the
motor's insulation.?
There are electronic overload relays with stall protection that will
protect a small motor like on a 4X6 but the cost of those relays approach
the cost of a replacement motor. If you are really worried about it and
are electronically inclined, you could make your? own stall protection
using something like an Arduino and mechanically sense a stalled
condition and will disconnect the motor. There is more to it since you
actually have to get the motor to start since it is stalled at start
which requires some type of controller beyond a toggle switch.
Personally, I will attend the operation of the machine since that is
easier and more likely foolproof.
On Mon, Feb 1, 2021 at 11:03 AM John Vreede
<vreededesign@...
> wrote:
- Good point Alan, the TE motors at least restrict the access to oxygen
to start a fire and the?? '....molten metal, burning insulation etc'
bit Jim quoted would be covered.
- However I don't know of any OEM TEFC motors on 4x6's, and do know
that at least one major manfr. is still using open motors.?? Has
someone got a new HF saw (HF is probably the biggest seller??), that can
say whether they use TEFC motors?
- This would be an additional thing to look for when buying - jv?
- On Tue, Feb 2, 2021 at 7:40 AM Alan Muller
<alan@...>
wrote:
- Do you consider that totally enclosed motors (TEFC) pose less of a
safety hazard than open (actually shielded) motors??? It seems
likely that an enclosed motor would be less likely to spew sparks and hot
metal than a motor with ventilation openings.
- I think I have noticed that equipment from Asia, even low priced
stuff, is likely to have a TEFC motor where conventional domestic
production (if there still were any) would not.
- am
- At 05:40 PM 2/1/2021 +0000, you wrote:
- John Wrote
- ??€?Don't think you should be concerned with UL certitification and
such.?? Induction motors have been around for 100yrs or so and the
things that make them fail aren't tested for in UL anyway ??????
- I would not go that far? ?? Safety certifications UL and other
wise (UL isn??€?t the only game in town)?? isn?sn??€?t so much about
t testing for things that make things fail, as testing to ensure that
WHEN they do fail, the fail ??€?relatively??€??????? safely. This
relatively safety includes not starting fires {??€??? ¡ molten ten
metal, burning insulation, fflaming particles, or other ignited material
could fall onto flammable material, or through which a flame could be
projected¡.??€???}
- > and not creating a shock hazard.
- ?
- A ??€?Listed??€??? or ??€ ??????Recognized??€??? motor (as compared
to an unlisted/recognized one)?? are far less likely to start a fire
or catch fire, when given the same amount of abuse.
- They are also less like to fail to live up to expectations as a
consequence of having to meet listing requirements.
- ? In particular a motor needs to fall within ~10% of the NEC values
for current for that size motor, at rated nominal voltage.
- There are also temperature rise tests, sheet metal thickness, and
grounding resistance tests.
- There is also a locked rotor test, For motors without a thermal
cutout this can run for 18 days, or until the motor fails. When it fails
(or at the end of the test if it doesn??€?t) there are temperperature
limits, and it still has to pass insulation resistance tests to
demonstrate that it has not created a shock hazard. For motors with a
thermal cutout, the test runs until the cutout operates. If the motor has
an auto-reset cutoff, then the test runs for 18 days.
- ?
- I have replaced the motor on my saw with a UL listed one. BUT I did
not do so until it failed.
- A saw that comes with a UL listed motor, is likely to be
significantly more expensive. If you are not using a flammable cutting
fluid, and make sure that both the motor and saw frame are grounded (and
that your plug has all 3 prongs.) I would not be worried. Just recognize
that the motor likely will die on you the moment you turn your back on it
- ?
- Also recognize that a ??€?CE??€??? markmark is in NO WAY a safety
certification mark like UL, CSA, ETL, etc
- ?
- R James (Jim) Klessig P.E. | Senior Power Systems Engineer |
- Electrical Reliability Services, VERTIV
- jim.klessig@...,
jim_klessig@...
- 1876 Gwin Rd, Mckinleyville | CA | 95519 | USA
- | Cell (707) 497-9611 | eFax 614-410-0653
- ?
- CONFIDENTIALITY NOTICE: This e-mail and any files transmitted with it
are intended solely for the use of the individual or entity to whom they
are addressed and may contain confidential and privileged information
protected by law. If you received this e-mail in error, any review, use,
dissemination, distribution, or copying of the e-mail is strictly
prohibited. Please notify the sender immediately by return e-mail and
delete all copies from your system.
--
John A. Schirra?
Sent from GMail
|