Re: Powering Three Phase Equipment in a Single Phase Shop
I’ve had two phase perfects. I bought them because I understood they provided cleaner power and I had invested a lot of money on my equipment and realized an electrical problem was something I
By Bill Belanger · #123666 ·
Re: Powering Three Phase Equipment in a Single Phase Shop
In my previous 1PH shop, i used a phase perfect converter, and it was superb.
By mike krockford · #123665 ·
Re: Powering Three Phase Equipment in a Single Phase Shop
Eric thanks for your response. What makes the phase perfect the better choice vs a rotary converter? Price is a consideration as I’ll have lots of other shop and house projects to do so if I can
By Dan Gavrilyuk · #123664 ·
Re: Powering Three Phase Equipment in a Single Phase Shop
Good luck with your move! I bought a Phase Perfect and it has worked very well. The specs are good, and when Felder learned I was installing a Phase Perfect, they didn;t bother having me send in the
By Eric Janson · #123663 ·
Powering Three Phase Equipment in a Single Phase Shop
After 4 years in my current commercial ship rental with three phase, I’m taking the plunge and buying a house with a 1k square foot detached garage. Closing is July 22, move will take place in
By Dan Gavrilyuk · #123662 ·
Re: #rfp - Random Friday Photo - June 3rd, 2022 #rfp
Only complaint, so far, on the door opener, control box supplied with no knock outs. Does not make any sense. It is not possible to use it w/o hooking it up to power, motors and sensors
By imran · #123661 ·
#rfp - Random Friday Photo - June 3rd, 2022 #rfp
Started install of Franklin Door Opener and wrapping steel frame. Imran Malik https://www.facebook.com/groups/362481112015700/?ref=share
By imran · #123660 ·
Re: Dual 51 Electrical Problem
It is amusing to see solutions without a clear problem statement. Imran
By imran · #123659 ·
Re: Dual 51 Electrical Problem
David, your reasoning is why I want the OP to check the output voltages to verify they are within spec for the machine. Motors might run on lower voltage but they tend to get hot, especially the
By David Kumm · #123658 ·
Re: Dual 51 Electrical Problem
Dave’s approach never worked for me - even by switching the 24V transformer tap inside the machines to boost the output to the control circuits and moving the PP manufactured leg around. I’m glad
By David P. Best · #123657 ·
Re: Dual 51 Electrical Problem
Now that the machine is up and running, I'd check the voltages between the three legs and see what you have ( T1-T2, T2-T3, T1-T3 ) . Compare to what is on the motor plate to see if you are within
By David Kumm · #123656 ·
Re: Dual 51 Electrical Problem
Terrence, Glad you are up and running. Since we really want to learn from each other I am not exactly sure what was your issue. One possibility is that the input to the PP was incorrect as described
By imran · #123655 ·
Re: Dual 51 Electrical Problem
All and especially Dave Kumm: Thanks for the input. I checked the PP documentation and determined the manufactured leg, traced it, swapped wires to keep the T3 from the machine controls (trial &
By Terence · #123654 ·
Re: Dual 51 Electrical Problem
fwiw, 208v is not "low voltage" in the sense of some defect.? ? It's just a different electrical distribution system.? It's very common in certain industries, for example, IT data centers. As
By mark thomas · #123653 ·
Re: Dual 51 Electrical Problem
David: Thanks for the tip, I called PP and they will not supply but agreed with the fix in concept. Will source one here locally. Terry
By Terence · #123652 ·
Re: Dual 51 Electrical Problem
Dave: I checked the 3 prongs at the plug, they read 120, 120, and 208…I have no idea how to move the 208 from the control circuit? The Dual spins the right way. Terry
By Terence · #123651 ·
Re: Dual 51 Electrical Problem
I had the same problem when I moved from Virginia (240 supply) to California industrial park (208 supply). The solution was a buck/boost transformer between the panel and the Phase Perfect. Phase
By David P. Best · #123650 ·
Re: Dual 51 Electrical Problem
I do not know industrial setups. It would definitely be worthwhile to measure all 3 outputs of the PP, phase to phase. My assumption was that PP is receiving 208VAC phase to phase, if such a thing
By imran · #123649 ·
Re: Dual 51 Electrical Problem
The code is flashed by a LED. Short pause when counting long pause end of digit. If the issue is low secondary voltages then the solution would be to change transformer. You are within +/-10% input
By imran · #123648 ·
Re: Dual 51 Electrical Problem
Check the output voltages on the PP. The 208v only applies to a three phase application with three legs measuring 120v to ground vs 240 delta where the third leg measures 208v. the two incoming legs
By David Kumm · #123647 ·