Wow, what a warm welcome.? Thank you all for the quick and thoughtful responses.? I did intend to say 'VFD' earlier, must have been a late night typo.?
?
In researching the Phase Perfect, it appears I can get by with smaller breakers on the single phase side, which it good since we've maxxed out our panel.? Now that Im leaning their direction, the question is which unit?? I'd like to stay with the 'Simple' line for cost savings, but Im confused on comparing the ratings between my machine nameplate and the options PP offers.?
?
My machine nameplate shows -?
- V 230.0
- PH:3
- HZ:60
- A:24
- KW: 7.35? S6-40%
The specs for the PTS are:
?
I'm deducing the machine is a 10HP from the 7.35KW rating.? I dont know what S6-40% means.?? From the PP specs the PTS005 appears to barely support the output (7.4kva), but the output amps are low - 18A when I require a max of 24.? Stepping up to the PTS007 appears to exceed both the KVA/KW requirements as well as the output amps.? However it still shows a rated HP of 7.5 which is confusing because that rating is lower than the stated output.
?
Simply put, will the PTS007 adequately power my Dual 51?? Are there any other reasons I should step up to the PP Enterprise line instead of the PP Simple?
?
Much appreciation for your expertise & input.