¿ªÔÆÌåÓý

ctrl + shift + ? for shortcuts
© 2025 Groups.io

Re: VFD issue with 3 Phase power supply


 

¿ªÔÆÌåÓý

I have not tried running the 5HP directly off 3 phase.? The currents out of the VFD into that motor are nearly identical.? As I understand it from reading on the issue, the VFD takes power in from 3 legs, converts to DC and then manufactures 3 phases of AC out.? It would not be too difficult to test the motor without the VFD.

?

Also this am I ran the bandsaw again (no VFD) and the current leg B (the one I¡¯m having trouble with) was a little lower than the other two.? A=9.65A, B=9.30A and C=9.60A.? Leg C is the wild leg.

?

From: [email protected] <[email protected]> On Behalf Of David Kumm
Sent: Friday, June 4, 2021 6:46 AM
To: [email protected]
Subject: Re: [FOG] VFD issue with 3 Phase power supply

?

Have you tried running directly from the utility three phase and checking the amp draw to see if it is uneven?? If that is the case it could be a motor issue.? Dave

?


From: [email protected] <[email protected]> on behalf of Joe Jensen <joe.jensen@...>
Sent: Friday, June 4, 2021 12:43 AM
To: [email protected] <[email protected]>
Subject: [FOG] VFD issue with 3 Phase power supply

?

I had to replace the VFD on my dust collector. It was an ABB ACS310 single phase input feeding a 3 phase 5 HP motor. This was from Oneida and because of the single phase supply they set the max current at the limit of the drive which is below the amperage of the motor. Anyway the new drive, an ABB ACS310 5HP 3 phase input VFD, faults with my utility delta 3 phase supply. The fault is due to uneven current on the input. I¡¯ve spent hours measuring and testing and worked with ABB tech support several times. The key test ABB had me do was to swap two wires to see if the low current moves. It does not so ABB said not the drive. But they did approve a warranty swap. With the replacement I see the same problem. With leg A I get 20A leg B 15A and leg C 19A. Leg C is the wild leg. The voltages under load for legs A and B are within 0.2V. I also had the utility out and then measured and said all good on their side. They did not put a scope on the lines to see is I have phase shift issues. Could a phase different between the lines cause a 20-25% current difference when the voltages are the same? ?Also I have notices that the current difference changes. Worst was tonight with 22A, 14A, and 20A.?


also I have two other 3 phase machines that run and the currents measure the same on all three legs for those machines. I also tried running the VFD with a new breaker and also on a different line. ABB agreed to swap the drive because the currents are the same on all legs with non-VFD machines. ?


the only thing I can think of is the phase angles between the three legs is not 120 degrees. HELP

Join [email protected] to automatically receive all group messages.