¿ªÔÆÌåÓýMitch, You can connect power to A1 & A2. do not connect any thing to dust collector. Confirm 15 & 16 are shorted and there is an open between 15 & 18. Now turn a machine on that has the coil installed. You should be able to verify that 15 & 18 are now shorted and there is an open between 15 & 16. This is what the dust collector switch needs to turn the DC on. Imran On Jan 9, 2021, at 9:39 PM, imranindiana via groups.io <imranindiana@...> wrote:
? Mitch, ? This is best I can think of. Maybe someone here will confirm. Run it by Felder before implementing it. <image001.png> Imran ? ? From: [email protected] On Behalf Of cmluck01 ? Imran, ? The dust collector motor is single phase and thus uses just two of the available 3 input lines at the contactor. The contactor is controlled by 240V for switching on/off. ? Thanks, Mitch ? ? On Sat, Jan 9, 2021 at 7:21 PM imranindiana via <imranindiana=[email protected]> wrote:
|