Joe,

I am not an expert but I am pretty sure this is not correct.

¡°?That's about 8KW of electric coming in that all turns to heat, either motor heat, or friction heat from cutting etc.¡±

Only a small portion of power being consumed is generating heat.

Imran

On May 22, 2020, at 7:48 PM, Joe Jensen <joe.jensen@...> wrote:

?Mark, I understand the thermal mass.? I often run the saw or shaper for an hour or two straight.? Sucking 110F air into my shop would definitely be a problem.? When running I have a 5HP dust collector and a 5HP saw, shaper, or sander running. That's about 8KW of electric coming in that all turns to heat, either motor heat, or friction heat from cutting etc.? My lighting is another 2.3kw.? 1kw of electric is 3412btu so 10kw of electric in is about 34K btu.? Over 3 tons of AC.? If I ran machines all the time and wanted to keep it cool when it's over 110F I would have had to have 10 tons of AC per the mechanical engineer.? That's without dumping exhaust outside.? Now if I were heating the machine heat would work for me and not against me.