Re: Problem with symbol TCP/IP Server on the CP4N

 

But you are technically using the CS, it is being used by the processor. As Lincoln indicated earlier, the processor sits behind the router along with anything you may have on the control subnet (much like your computer is behind the router on your home network).
Exactly. If the server is initialized before the processor pulls an IP address, DNS etc. it will fail, plain and simple. Do what the others have suggested and I'm 99.9% certain it will fix your issue. The reason a program reset works is because the control subnet router is already running and the processor can pull an IP address to start your server, whereas on a hardware reset or reboot it will never work.?

I would definitely encourage on processors with control subnet to set your startprogafterrouter to on, mostly because you don't have behind the scenes control of every module or device trying to connect, initialize etc. I thought this was changed to default ON but I may be mistaken.


Re: Dm-NVX not liking hex IP-ID

 

Did you try just entering in E instead of 0E?


Dm-NVX not liking hex IP-ID

 

weird D-30 gives error with IP-ID 0E but accepts IP-ID 20--seem to remember some mention of this or similar


Re: Problem with symbol TCP/IP Server on the CP4N

 

¿ªÔÆÌåÓý

But you are technically using the CS, it is being used by the processor. As Lincoln indicated earlier, the processor sits behind the router along with anything you may have on the control subnet (much like your computer is behind the router on your home network).

?

Caleb Radecky | Manager, Online Products & Services
Crestron Silver Certified Programmer | DMC-D-4K | DMC-E-4K
ControlWorks Consulting, LLC | Crestron Services Provider | 8228 Mayfield Rd. #6B Rear Cleveland OH 44026
D. 440.771.4809 | O.440.449.1100 X1109 | F.440.449.1106 |

?

From: [email protected] <[email protected]> On Behalf Of nvc84 via groups.io
Sent: Monday, October 9, 2023 15:32
To: [email protected]
Subject: Re: [crestron] Problem with symbol TCP/IP Server on the CP4N

?

Thanks for your reply. But in our case, the Control Subnet port on the CP4N processor is not used at all! All equipment is located on the LAN port.


Re: VC-4 & Sonos

 

I did this recently
Player names must be exactly the same
Order of the module matters (init needs to be above all others, followed by device modules)
Remove all characters that are not A-Z,a-z?
it doesn't seem to like spaces.?
You may need to delay the module initialization?till after a minute.?


On Fri, Sep 22, 2023 at 11:30?AM nicofreda <cdandcontrol@...> wrote:
thanks, so I guess that If I use a rmc3 instead of the vc4, no port issues right?
nf


Re: Problem with symbol TCP/IP Server on the CP4N

 

So you tried it and it made no difference at all?


On Monday, October 9, 2023, nvc84 via <nvc84=[email protected]> wrote:
Thanks for your reply. But in our case, the Control Subnet port on the CP4N processor is not used at all! All equipment is located on the LAN port.


Re: Problem with symbol TCP/IP Server on the CP4N

 

Thanks for your reply. But in our case, the Control Subnet port on the CP4N processor is not used at all! All equipment is located on the LAN port.


Eikos 4K - Supplement Solution?

 

Im getting feedback that Analogway Eikos 4k are having supply chain issues, And I have project in need of one any recommendations for alternates on anyone not having supply issues this year?


Re: Problem with Voice Control

 

Good morning Dave, Tony,

I updated the firmware to?1.8001.5061.29979 but the problem persists. After the update-reboot sequence some notices started showing up in the error log about SSL Certificates. I confess I don't know exactly what those notices mean or if they are in any way related to the client's problem. But?as of right now the voice control system still does not connect. System is registered but not connected. (The first column on the admin portal says "registered").?
We tried to delete and re-register but the result is the same: a timeout local error after 30 seconds of registration.

Netstat remains the?same, we see a connection being made to?13.82.93.245 on port 443, but it never gets to be established. It remains on time_wait state for a while then closes.

Maybe the problem is in these certificates? Anyone know about this?

I thank you again for taking the time to help me with this issue, both of you.

Daniel Arola

?SYSTEM LOG:
? 1. Notice: nk.exe # 2023-10-09 11:48:19 ?# 11:48:01 10-09-2023: DIN-AP3 v1.8001.0214 Application watchdog fault: ConsoleServiceCE(1) ?2. Notice: nk.exe # 2023-10-09 11:48:19 ?# System startup: DIN-AP3 [v1.8001.0214 (Nov 10 2022) #00D0E2CB]
? 3. Notice: nk.exe # 2023-10-09 11:48:19 ?# HDG: Timeout set from registry 2 minutes
? 4. Notice: ConsoleServiceCE.exe # 2023-10-09 11:48:40 ?# GHS_ProcessCertificate: Cert "TrustCor ECA-1" serial "84822C5F1C62D040" not found, adding to GHS
? 5. Notice: ConsoleServiceCE.exe # 2023-10-09 11:48:42 ?# GHS_ProcessCertificate: Cert "TrustCor RootCert CA-1" serial "DA9BEC71F303B019" not found, adding to GHS
? 6. Notice: ConsoleServiceCE.exe # 2023-10-09 11:48:43 ?# GHS_ProcessCertificate: Cert "TrustCor RootCert CA-2" serial "25A1DFCA33CB5902" not found, adding to GHS
? 7. Notice: ConsoleServiceCE.exe # 2023-10-09 11:48:44 ?# GHS_ProcessCertificate: Cert "Trustwave Global Certification Authority" serial "05F70E86DA49F346352EBAB2" not found, adding to GHS
? 8. Notice: ConsoleServiceCE.exe # 2023-10-09 11:48:45 ?# GHS_ProcessCertificate: Cert "Trustwave Global ECC P256 Certification Authority" serial "0D6A5F083F285C3E5195DF5D" not found, adding to GHS
? 9. Notice: ConsoleServiceCE.exe # 2023-10-09 11:48:45 ?# GHS_ProcessCertificate: Cert "Trustwave Global ECC P384 Certification Authority" serial "08BD85976C9927A48068473B" not found, adding to GHS
?10. Notice: ConsoleServiceCE.exe # 2023-10-09 11:48:46 ?# GHS_ProcessCertificate: Cert "T-TeleSec GlobalRoot Class 2" serial "01" not found, adding to GHS
?11. Notice: ConsoleServiceCE.exe # 2023-10-09 11:48:47 ?# GHS_ProcessCertificate: Cert "T-TeleSec GlobalRoot Class 3" serial "01" not found, adding to GHS
?12. Notice: ConsoleServiceCE.exe # 2023-10-09 11:48:48 ?# GHS_ProcessCertificate: Cert "TUBITAK Kamu SM SSL Kok Sertifikasi - Surum 1" serial "01" not found, adding to GHS
?13. Notice: ConsoleServiceCE.exe # 2023-10-09 11:48:48 ?# GHS_ProcessCertificate: Cert "TWCA Global Root CA" serial "0CBE" not found, adding to GHS
?14. Notice: ConsoleServiceCE.exe # 2023-10-09 11:48:49 ?# GHS_ProcessCertificate: Cert "UCA Extended Validation Root" serial "4FD22B8FF564C8339E4F345866237060" not found, adding to GHS
?15. Notice: ConsoleServiceCE.exe # 2023-10-09 11:48:50 ?# GHS_ProcessCertificate: Cert "UCA Global G2 Root" serial "5DDFB1DA5AA3ED5DBE5A6520650390EF" not found, adding to GHS
?16. Error: ConsoleServiceCE.exe # 2023-10-09 11:48:50 ?# Couldn't find beginning or ending tags
?17. Error: ConsoleServiceCE.exe # 2023-10-09 11:48:51 ?# Couldn't find beginning or ending tags
?18. Warning: ConsoleServiceCE.exe # 2023-10-09 11:48:57 ?# Cleared blocked/locked lists on Console Service startup
?19. Notice: ConsoleServiceCE.exe # 2023-10-09 11:49:16 ?# SHELL Connection from: 192.168.0.140
?20. Warning: CPHProcessor.exe # 2023-10-09 11:49:34 ?# CPHPlugin: getInstance()
?21. Notice: CPHProcessor.exe # 2023-10-09 11:49:34 ?# CresStore: Connections OK to redis
?22. Notice: HydrogenManager.exe # 2023-10-09 11:49:50 ?# CresStore: Connections OK to redis
?23. Notice: SimplSharpPro.exe # 2023-10-09 11:50:10 ?# Firmware does not support updating of the Write Priority at runtime. Minimum firmware version to make this feature work is 1.8002.0
?24. Notice: SimplSharpPro.exe # 2023-10-09 11:50:12 ?# Starting Programs...!
?25. Notice: SimplSharpPro.exe # 2023-10-09 11:50:14 ?# Flash Policy Server - Starting Server.
?26. Notice: SimplSharpPro.exe # 2023-10-09 11:50:14 ?# Flash Policy Server - Server Started.
?27. Notice: LogicEngine.exe # 2023-10-09 11:50:40 ?# **Program 1 Started**
?28. Notice: TLDM.exe # 2023-10-09 11:50:42 ?# ?Event rcvd is 8
?29. Error: LogicEngine.exe [App 1] # 2023-10-09 11:51:11 ?# Did not receive End of Query Acknowledge from device at Slot-02.IP-ID-16.Slot-01.ID-52.
?30. Warning: ConsoleServiceCE.exe # 2023-10-09 11:53:18 ?# SHELL connection being closed from address 192.168.0.140.

?31. Notice: ConsoleServiceCE.exe # 2023-10-09 11:53:23 ?# SHELL Connection from: 192.168.0.140
?32. Notice: ConsoleServiceCE.exe # 2023-10-09 11:55:21 ?# SHELL Connection from: 192.168.0.140
?33. Error: splusmanagerapp.exe [App 1] # 2023-10-09 11:55:47 ?# 10/9/2023 11:55:47 AM ConnectionManager.Connect: Exception occurred during connection.? Exception:System.Exception: Websocket client connect: Exception Thrown = (NullReferenceException)
? ?at Crestron.SimplSharp.CrestronWebSocketClient.WebSocketClient. 34. Error: splusmanagerapp.exe [App 1] # 2023-10-09 11:55:47 ?# Connect()
? ?at Crestron.RemoteService.SessionManager.ConnectionManager.Connect()
? ?at Crestron.RemoteService.SessionManager.ConnectionManager.Send(Byte[] messagebytes)
? ?at Crestron.RemoteService.SessionManager.SessionManager.Send(Byte[] message)
? 35. Error: splusmanagerapp.exe [App 1] # 2023-10-09 11:55:47 ?# ? at Crestron.RemoteService.MessageManagement.MessageManager.GenerateRequest(String requestedAction, Dictionary`2 parameters, ResponseCallback callback, Int64 transactionID)
? ?at Crestron.RemoteService.SessionManager.SessionManager.SendRegister(String r 36. Error: splusmanagerapp.exe [App 1] # 2023-10-09 11:55:47 ?# egistrationCode, ResponseCallback callback, Object callbackCustomObject)
? ?at Crestron.RemoteService.SessionManager.SessionManager.SendRegister(String registrationCode)
? ?at Crestron.RemoteServiceSimpl.SessionManagerSimpl.SendRegister(String registrat 37. Error: splusmanagerapp.exe [App 1] # 2023-10-09 11:55:47 ?# ionCode)
? ?at CrestronModule_REMOTE_SERVICE_CONNECTION_MANAGER_V2_0_0.CrestronModuleClass_REMOTE_SERVICE_CONNECTION_MANAGER_V2_0_0.REGISTRATIONCODE_OnChange_3(Object __EventInfo__)
? ?at Amib.Threading.Internal.WorkItem.n()
? ?at Amib.Threading.Intern 38. Error: splusmanagerapp.exe [App 1] # 2023-10-09 11:55:47 ?# al.WorkItem.Execute()
? ?at Amib.Threading.SmartThreadPool.f(WorkItem A_0)
? ?at Amib.Threading.SmartThreadPool.r()
?

?39. Error: splusmanagerapp.exe [App 1] # 2023-10-09 11:56:16 ?# 10/9/2023 11:56:16 AM SessionManager.RegisterCallback: Registration failed, ResultCode:100-TimedOutLocal?

On Fri, Oct 6, 2023 at 4:22?PM Dave H - Crestron True Blue Tech Support Engineer Since 2014 via <dhollander=[email protected]> wrote:

Agreed. A FW update is likely needed for compatibility, based on timeframes shown in release notes.
3-Series FW v1.503 is from 2018, while Voice Control v2.x modules are from Mar.2021.


Re: Problem with symbol TCP/IP Server on the CP4N

 

¿ªÔÆÌåÓý

STARTPROGAFTERROUTER ON should fix this for you.

?

Under the hood there are two different components ¨C the processor and the router. The processor sits behind the router along with anything you may have on the control subnet (much like your computer is behind the router on your home network)

?

What is happening is that on a CP4N/etc. the program is getting started before the router is fully initialized ¨C I¡¯m guessing to help speed processor boot times and because a lot of times this doesn¡¯t matter ¨C but there are some cases, like a TCP server where if the program starts before the router there can be undesired results ¨C I¡¯m guessing if you tried connecting to the TCP server from the CS it would be more likely to work. In any event STARTPROGAFTERROUTER ON should fix this for you by delaying program startup until the router is ready

?

Lincoln

?

--

Lincoln King-Cliby

Commercial Market Director
Sr. Systems Architect | Crestron Certified Master Programmer (Diamond)
ControlWorks Consulting, LLC
Direct: (+1)440.771.4807 | Cleveland: (+1)440.449.1100? | Boston: (+1)508.695.0188 | DC: (+1)202.381.9070?
Crestron Services Provider | Biamp Authorized Independent Programmers | Extron Qualified Independent Programmer

?

?

From: [email protected] <[email protected]> On Behalf Of nvc84 via groups.io
Sent: Saturday, October 7, 2023 7:24 AM
To: [email protected]
Subject: [crestron] Problem with symbol TCP/IP Server on the CP4N

?

Hi!
The TCP/IP Server symbol (port 888) does not work on the processor CP4N after a hard reset or power cycle. But it works when the program is restarted.?A program consisting of only this one symbol behaves similarly - TCP connection error 10061.?All this works perfectly on RMC4.??


Re: Barco Alchemy (AKA DP2K-6E) Projector Standby/Wake commands?

 

Hi Michael!

We purchased Josh's module and have it working great for controlling the ICMP (had to downgrade from a 4 series to 3 series to make it work but that's OK - it's a known issue with later 4 series processors). But the module is good for lamp, dowser and macros only, NOT overall power. When I asked Josh about it he told me he'd decided not to include it because this actually powers down the ICMP card and then you have to deal with timing issues giving it enough time to warm up before talking to it. Plus he wasn't sure if the commands were even available.

I've got a case going with Barco...they of course initially just sent me the same document as I already had. I asked them to please dig deeper and ask around. And I got the commands wrong when I first posted. it's actually

\xfe\x00\x66\x66\xff? ? ?put it in sleep mode
\xfe\x00\x67\x67\xff? ? ?take out of sleep mode

These at least respond with an "ack" but nothing actually seems to happen.

it will be interesting to see where this goes, Barco will either deny it's even possible or just say it *should* work and yet, somehow automagically the existing Control4 system is doing it via IP, there are no GPIO signals connected.


OP


Re: Simpl+ arrays comparison

 

a little not what I wanted, but you gave useful advice. Thank you.


Re: What are Alexa Scenes in the Voice Control Room Lights module?

 

On Thu, Oct 5, 2023 at 11:46 PM, Dave H - Crestron True Blue Tech Support Engineer Since 2014 wrote:
"Alexa, ask/tell Crestron to recall <SCENE> in <ROOM>" (ie "morning scene in kitchen")
It's so long phrase.

I use Alexa Routines. For example, phrase (routine) "Alexa, hello!" start macros with voice greeting and execute some long command/commands.


Re: Simpl+ arrays comparison

 
Edited

It will look something like this:




#Define_Constant MaxElements 20

Digital_Input Test

String Array1[MaxElements][8],
Array2[MaxElements][8];
Integer Array3[130];

Push Test
{
Integer i;
SetArray(Array3, 0);
For(i = 1 to MaxElements)
{
If(Array1[i] != Array2[i]
{
Array3[AtoI(Array1[i]] = AtoI(Array2[i]);
}
}
}


Re: Simpl+ arrays comparison

 

Yes, I only need the numbers of matching elements of the arrays from which to build array3


Re: Simpl+ arrays comparison

 

Are you just trying to see if each element of array1 and arra2 equal each other? If they don't converter them to integers, using array1 as the element and array2 as the value for array3?


Simpl+ arrays comparison

 
Edited

Have a nice day, everyone.
there is a task, the meaning is below:

string array1[a][8];
string array2[b][8];
integer array3 [c];? ? ? ? ? ? ? ? ? ? ? ? ? ?//you need to create a third array by iterating over all the strings in array1 and array2
//we need to find a way to compare all the lines -? ?a=1 to 130, b=1 to 130//
IF (Comparestring (array1[a],array[b])=0)
{array3[a]=b;}
Is it possible to solve this problem using Simpl+??
I will be grateful for your help



Re: Barco Alchemy (AKA DP2K-6E) Projector Standby/Wake commands?

 

Do you have a link for this module? I searched around a bit and couldn¡¯t find it online?


Re: Problem with symbol TCP/IP Server on the CP4N

 
Edited

Thanks for your reply. But I still don't understand why the processor works fine when we just restart the program and doesn't work immediately after turning on the power. This is almost the same as if every time you turn it on you have to first restart the Windows operating system. In addition, why do tcp-clients always work on the processor, but this strange exception is made for the tcp- server? P.S.?And why did this same program work fine on Pro3 before?


Re: Problem with symbol TCP/IP Server on the CP4N

 

On Sat, Oct 7, 2023 at 11:42 AM, Dave H - Crestron True Blue Tech Support Engineer Since 2014 wrote:
Did you set STARTPROGAFTERROUTER ON?
Dave, is this something that you recommend to be run for all 'N' processors? of is this just to try to solve this issue?? TIA!

Though I expressly forbid the 'N' units on our projects, we did have a couple over the years that we dealt with, because of *stuff*, so I'm interested in this generally...