Re: Crestron CP4 and Lutron Athena through RS-232


 

Hello Group,

?

To close this topic?:

Phantom keypad could be under control if they are ¡°linked to the QSE-CI-NWK-E interface¡±, this is not by default and needs to be done by the Lutron programmer.

Once available through the IP/RS-232 interface, the #DEVICE, Integration ID, Component Number, Action Number, Parameters\x0D\x0A command could be use:

  • The Integration ID is available in the Lutron Integration report (provided by the Lutron programmer),
  • The Component Number is the button number (1, 2, 3 etc¡­),
  • I use the Action Press and Release so 3 for Press and 4 for Release to mimic a button press and release,
  • No Parameter in that case.

?

So by sending #DEVICE,89,1,3\x0D\x0A #DEVICE,89,1,4\x0D\x0A, I mimic an press and release of the first button of the phantom keypad at ID 89. Whatever was programmed in the Lutron system for that button will fire ?.

?

Problem solved, thanks All ?.