The issue occurs with Simpl programs too, not just Crestron Home. However, it's usually easier to come up with a work-around with Simpl.
The problem is caused by the INET-IOEX-RYIO not reporting its input states on program start, so a closed or shorted input will show as open after a program reboot. Correcting the feedback will require either opening then closing the input again, or power-cycling the IOEX.
I normally run the IOEX's power through one of the relays, if they aren't both being used, then program that relay to always be on. That will cause a temporary interruption of power whenever the program restarts, and refresh the inputs' status. If both relays are being used, some other method could be used to reboot the IOEX, or I suppose rebooting the RF gateway would also work - although I haven't tried that.
toggle quoted message
Show quoted text
--- On Friday, January 8, 2021 at 11:29 AM, Evan Kontos wrote:
Ive been using that IOEX for garage doors and it depends upon whether youre
doing it with PYNG or with Simpl. When you first start the system PYNG is
confused with the signal it receives as to whether the door is open or
closed. You have to cycle it once to make sure. THAT is a problem if you are
remote and trying to open your door remotely. A camera in the garage would be
good in addition to the magnetic contact for safety purposes.