¿ªÔÆÌåÓý

ctrl + shift + ? for shortcuts
© 2025 Groups.io

Re: How many digital signals can you pulse from one source?


 

What does debugger say is happening?

On Fri, Jul 7, 2017 at 4:46 PM, B B bb2479av@... [Crestron] <Crestron@...> wrote:
?

Hi Lincoln,

?The toggle is only fired by two steppers for different modes and a stepper for off. No other signals are driving it.


On Jul 7, 2017, at 4:19 PM, Lincoln King-Cliby lincoln@... [Crestron] <Crestron@...> wrote:

?

Not at all likely unless you have one heck of a lot of other stuff happening at the same time. The maximum number of signals that can change on a single logic wave is in the tens of thousands.

?

If the toggle is not behaving consistently I¡¯d look at the inputs ¨C make sure you aren¡¯t holding the other inputs on the toggle (SET, RESET, TOGGLE) high and also make sure that the output of the toggle isn¡¯t jammed with anything else that could make it appear that it¡¯s not working.

?

--

Lincoln King-Cliby, CTS, DMC-E-4K/T/D
Commercial Market Director
Sr. Systems Architect | Crestron Certified Master Programmer (Gold)
ControlWorks Consulting, LLC
V: (+1)440.449.1100 x1107 F: (+1)440-449-1106 I:
Crestron Services Provider | Biamp Audia Certified | Extron Authorized Programmer

?

From: Crestron@... [mailto:Crestron@yahoogroups.com]
Sent: Friday, July 07, 2017 3:01 PM
To: Crestron@...
Subject: [Crestron] How many digital signals can you pulse from one source?

?




Hi Guys,

?

?I have a strange issue with a CP3N. It is not operating a toggle consistently on shutdown. About every tenth shutdown it doesn't operate the toggle. I'm pulsing the toggle from a stepper. I've tried different times, formats to no avail. I noticed that I have six or so digital signals on my Clear Routes digital pulse. Is that too many?

?

Thanks.

?

?





Join [email protected] to automatically receive all group messages.