Lutron Leap broken in SIMPL 4.20


 

Hopefully I can save someone else a bit of time and headache with this info.? I found out today that the latest SIMPL 4.20 and latest databases causes Lutron leap integration to stop working.? I ended up setting up a test machine with SIMPL 4.18 and have it working again.? I'm busy trying to commission a job today and didn't have time to fully dissect this issue, but I'm sure its bound to affect others.

I did spend time on the phone today with TB support and they weren't aware of the issue.? Of course.

Here's the software info that is working.?

?

SIMPL Windows: 4.18p1 (build: 4.1801.16)
SIMPL+ 4.06 (build: 4.0600.00)
Path: C:\Program Files (x86)\Crestron\Simpl

INCLUDE4_2SERIES.DAT Version Information:
(2 Series) : 1.80

INCLUDE4.DAT Version Information:
(3 & 4 Series) : 2.18.015

Data Files:
Path: C:\Program Files (x86)\Crestron\Cresdb\Programming

Symlib2.Tio 1156 11/19/2021 02:19:02PM

iodev.tio 1156 11/19/2021 02:19:02PM

Other Crestron SW:

Device Database: 200.140 (build: 200.14000.001.00)
Crestron Database (cnctrldb22000.mdb) : 210.05 (build: 210.0500.001.00)
Crestron Toolbox: 3.11p20 (build: 3.1120.0030.0)
SIMPL+ Cross Compiler: 1.3

Legacy Device Tools: Not Available

Windows System Information:
Windows OS: Windows 10 Home Version 2009 (OS Build 19042.1526)


 

开云体育

Yes, the SecureTcpClient that is used by the Lutron Leap Modules (QSX…} is malfunctioning with the latest DB updates. You do not have to role back all the software however.

The include4 is the culprit! Crestron has been informed of the problem, and Toine is having someone look into it.

To get it working, you just need to compile against the lInclude4 {2.18.112).. It is easy to replace. Control Concepts, has it saved off if anyone needs it. This should?affect?other libraries that use the SecureTcpClient.

You can request the include4 by emailing projects@....

Jeff



 

开云体育

Jeff

I'm not familiar with SecureTcpClient.? Are you saying that any module that uses an https client connection to a device is affected?

Thanks

Jay

On 9/30/2022 5:02 AM, jeff via groups.io wrote:

Yes, the SecureTcpClient that is used by the Lutron Leap Modules (QSX…} is malfunctioning with the latest DB updates. You do not have to role back all the software however.

The include4 is the culprit! Crestron has been informed of the problem, and Toine is having someone look into it.

To get it working, you just need to compile against the lInclude4 {2.18.112).. It is easy to replace. Control Concepts, has it saved off if anyone needs it. This should?affect?other libraries that use the SecureTcpClient.

You can request the include4 by emailing projects@....

Jeff



 

The SecureTcpClient is a raw SSL stream connection, sister to the standard TcpClient. The https does use SSL but, I don’t believe uses this connection class internally. We have not seen this issue with the https client. The SecureTcpClient is used when SSL is needed that does not use the HTTP protocol.


 

开云体育

Thanks Jeff!

On 9/30/2022 6:51 AM, jeff via groups.io wrote:

The SecureTcpClient is a raw SSL stream connection, sister to the standard TcpClient. The https does use SSL but, I don’t believe uses this connection class internally. We have not seen this issue with the https client. The SecureTcpClient is used when SSL is needed that does not use the HTTP protocol.


 

Thanks Jeff!? I was able to get it working using the include4.dat file from my test machine.? Copied into the C:\Program Files (x86)\Crestron\Cresdb\Programming folder


 

Include4.dat v2.18.112 corresponds with DevDB v200.205.001.
?

No need to manually manipulate files or roll back *all* software.
Easiest to just uninstall DevDB & then download/install the older version from FTP server.
?


 

On Fri, Sep 30, 2022 at 02:56 PM, Dave H - Crestron TS wrote:

Include4.dat v2.18.112 corresponds with DevDB v200.205.001.
?

No need to manually manipulate files or roll back *all* software.
Easiest to just uninstall DevDB & then download/install the older version from FTP server.
?

Is it not time to completely remove the 3-series sandbox yet? It's nearly 2023, and the sandbox really doesn't do much... Why do we *need* it again? :/
?
--
?
Crestron Service Provider - TBD Enterprises Inc.


 

Troy,
Though I don't fully understand the intricacies of what this thread is discussing, don't we need to maintain 3-series elements for the foreseeable future due to 3-series system maintenance and supply chain issues forcing us to rely on 3-series processors (often used) to get projects finished for the time being??
I may be completely missing what you're saying so please educate as necessary...:)? TIA!


 

Does todays update help with this Lutron issue?


Version:?200.220.001.00?
Last Modified:?10/4/2022 12:00:00 PM??
MD5 Hash:?
?

Change Log:
Fixes/Changes from 200.215.002 to 200.220.001:
MD5 Hash: d5c5b3326875478344fce6fb91bb787d


Library Update
  • Updated
    • DIN-1TSTAT8
    • HD-MD4x1-4KZ-E/HD-MD4x2-4KZ-E/HD-MD4x4-4KZ-E/HD-MD8x4-4KZ-E/HD-MD8x8-4KZ-E
    • INCLUDE4.DAT (3 & 4 series) version 2.19.016
      • Update the DIN-1TSTAT8 SSP class to add the new Temp Offset joins
      • Priority & Auto route on & off changes for HD-MD-NxM-4KZE


 

Just tested the new database. Include 2.19.016 does not fix the issue


 

Finally got around to testing the new database this morning and the include4.dat issue has been fixed in version 2.19.022.

?

Compiled On:? 11/15/2022 9:14 AM
Compiler Rev: 3.03
CrestronDB:?? 214.05.004.00
DeviceDB:???? 200.230.001.00
SYMLIB Rev:?? 1176
IOLIB Rev:??? 1176
IOPCFG Rev:?? 4.1.75
Source Env:?? SIMPL Windows v4.2000.00
Target Rack:? AV4
Config Rev:?? 22
Include4.dat: 2.19.022
Friendly Name:Lighting