I had done a system like that multiple processors talking to a master processor. You can use UDP for all of your system creating a custom protocol with an header? who identify the message is dedicated to which processor.?

Or you can create a TCP server on your processor with a port range and each processor based on their IP address connect to a specific port.

RThiffault


Le mer. 15 nov. 2023, 13 h 59, Charles Jones via <mokasa=[email protected]> a ¨¦crit?:
I forgot to mention, we have about 50 spaces, each with CP4N, and I'm working on getting all of them on the exact same program that I'll be able to mass load. Plus, the head-end Pro4 manages all the NVX's in the building (they didn't buy a Director), and I only have 83 IPID's left, which is why I wasn't trying to do the separate IPID thing. We also plan on adding at least 20 rooms in the new part of the building, along with many more NVX's, so I'm trying to make it expansion-ready.

For my application, I was just having it refresh the text only when the remote processors push the tuner control button, so timing shouldn't be an issue.

I guess a TCP/IP Server/Client with xsig would work, so I may go that route, especially since it's very unlikely that all rooms would be pressing the tuner control button at the same time.