2 series as a slave are CIP. They're not Gateway. As such you have to put the IP Entry in the IP config tab in SIMPL before you compile it if you expect to upload it w/the program, or you can do it via toolbox like you did.
No magic, it's expected behavior, and they should know that.
toggle quoted message
Show quoted text
--- In Crestron@..., "Kris" <kris.k@...> wrote:
When I compile and load the program to the cp3 the ip table does not include the eslaved pro2. If I manually enter the ip table entry it works fine, however the pro2 shows up as CIP instead of gateway. Anyone run into this? TB support said they would "tap some shoulders" and get back to me.